What are the contact configurations for this contactor?
The contactor has a 3NO (3 Normally Open) contact configuration, suitable for a variety of applications in controlling motor loads.
What is the rated operational current of this contactor?
The rated operational current for the DIL0AM contactor is 22.5 A at 400 V ac in AC-3 utilisation category.
Can this contactor be used for DC applications?
Yes, the contactor can switch DC currents, with specific ratings depending on the voltage level. Please refer to the datasheet for detailed DC operation specifications.
What is the rated insulation voltage for this contactor?
The rated insulation voltage (Ui) for this contactor is 690 V AC.
What is the mechanical lifespan of this contactor?
The mechanical lifespan of the contactor is rated at 10 million operations, ensuring long-term reliability in mechanical switching.
What is the degree of protection provided by this contactor?
This contactor provides a degree of protection of IP20, safeguarding against solid objects larger than 12.5 mm but not against water.
What are the ambient temperature limits for this contactor?
The contactor can operate in ambient temperatures ranging from -25°C to +50°C when open and -25°C to +40°C when enclosed.
What are the terminal capacities for this contactor?
The terminal capacities for the main cable are 1 × (0.75 – 4) mm2 solid or 2 × (0.75 – 4) mm2 flexible with ferrule, and for control circuit cables are 1 × (0.75 – 4) mm2 solid or 2 × (0.75 – 2.5) mm2 flexible with ferrule.
What is the power consumption of the coil at cold coil and 1.0 × Uc?
The power consumption of the coil at cold coil and 1.0 × Uc for AC pick-up is 67 VA and for sealing is 8.5 VA at 50 Hz. For DC, the power consumption for both pick-up and sealing is 9.5 W.
What is the making capacity of this contactor?
The making capacity of the contactor is 200 A for cos φ according to IEC/EN 60947.
Can this contactor be used for capacitor switching?
Yes, the contactor can be used for individual compensation of three-phase capacitors with specific rated operational currents. Please consult the datasheet for precise values.