What is the function of this Emerson power supply?
The Emerson Dual DC Power Supply is designed to provide stable DC power to electronic components within a control system. It converts input power to the required levels of DC power for various components.
Can this power supply be used in hazardous environments?
Yes, the power supply is suitable for use in hazardous atmospheres and is rated II 3 G, with specific installation and operation instructions for such environments.
What are the input voltage requirements for this power supply?
The power supply can accept an input voltage of 11.5 VDC to 12.6 VDC or 19.2 VDC to 28.8 VDC, depending on the system requirements.
What is the output power rating of the power supply?
The output power rating is 10.2 W total at 70°C, with combined outputs of 5 VDC and 3.3 VDC.
What are the environmental specifications for this power supply?
The power supply can operate in ambient temperatures ranging from -40 to 70°C, with a relative humidity of 5% to 95% non-condensing. It is also resistant to shock, vibration, and airborne contaminants.
Is there any maintenance or calibration required for this power supply?
No, the unit contains no user serviceable parts and does not require disassembly or calibration.
Can the power supply be hot-swapped while the system is energised?
No, the unit must not be removed or inserted while system power is energised. It should be powered down before any removal or insertion is performed.
What are the safety approvals for this power supply?
The power supply has safety approvals for Class I Division 2 Groups A, B, C, and D hazardous locations with a temperature rating of T4.
What should be considered when installing this power supply in a control system?
When installing the power supply, it is important to follow the specific instructions for installation in hazardous areas and ensure that the voltage source does not exceed the specified limits.