What are the power supply requirements for the IM 253DPO Profibus-DP slave?
The power supply required is DC 24 V with a permitted range of DC 20.4 to 28.8 V. It includes reverse polarity protection and has a no-load operation current consumption of 70 mA. The rated value for current consumption is 1 A.
Can the IM 253DPO operate in different environmental conditions?
Yes, the IM 253DPO is designed to operate within a temperature range of 0 °C to 60 °C and can be stored in temperatures ranging from -25 °C to 70 °C.
What type of interface does the IM 253DPO use for communication?
The IM 253DPO uses a fibre optic cable (FOC) interface for communication, specifically with a 2-pin FOC POF/HCS connector.
How many modules can be connected to the IM 253DPO?
The IM 253DPO can support a maximum of 32 modules per rack, with a limitation of 16 analog modules.
What diagnostic features does the IM 253DPO offer?
The IM 253DPO provides comprehensive diagnostic features that are parameterizable, including status display, interrupts, process alarms, diagnostic interrupts, and the ability to read out diagnostic information.
What is the maximum transmission speed of the IM 253DPO?
The maximum transmission speed of the IM 253DPO is 12 Mbit/s, with the minimum being 9.6 kbit/s.
How is the IM 253DPO mounted?
The IM 253DPO is designed to be mounted on a standard 35 mm profile rail.
What are the dimensions and weight of the IM 253DPO?
The dimensions of the IM 253DPO are 25.4 mm in width, 76 mm in height, and 78 mm in depth, and it weighs approximately 110 g.
What certifications does the IM 253DPO hold?
The IM 253DPO holds a UL508 certification.
What is the maximum number of node addresses supported by the IM 253DPO?
The IM 253DPO supports node addresses ranging from 1 to 99.