steve
Got hold of Sime for a Carrier card for…
Got hold of Sime for a Carrier card for a chiller. Machine down in a factory. Received the new card in express time machine and plant now up and running fantastic service form Sime
3 weeks ago
Full 12-month warranty
Available for dispatch immediately
We deliver worldwide
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
All orders are subject to product availability. See our T&Cs.
Ask our team
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
| Specification | Description |
|---|---|
| Part Number | GV2P05 |
| Manufacturer | Schneider |
| Product Type | Circuit Breaker |
| Poles | 3 Pole |
| Rated Operational Current | 1 A |
| Rated Operational Voltage | 690 V ac |
| Dimensions | 45 x 97 x 89 mm |
| Network Type | AC |
| Utilisation Category | AC-3 conforming to IEC 60947-4-1 |
| Trip Unit Technology | Thermal-magnetic |
| Breaking Capacity | 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Rated Service Short-Circuit Breaking Capacity | 100% at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Control Type | Rotary handle |
| Thermal Protection Adjustment Range | 0.63…1 A conforming to IEC 60947-4-1 |
| Magnetic Tripping Current | 13 A |
| Rated Insulation Voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947-2 |
| Phase Failure Sensitivity | Yes conforming to IEC 60947-4-1 |
| Suitability for Isolation | Yes conforming to IEC 60947-1 § 7-1-6 |
| Power Dissipation per Pole | 2.5 W |
| Mechanical Durability | 100000 cycles |
| Electrical Durability | 100000 cycles for AC-3 at 415 V In |
| Tightening Torque | 1.7 N.m - on screw clamp terminal |
| Colour | Dark grey |
| IP Degree of Protection | IP20 conforming to IEC 60529 |
| Operating Altitude | Up to 2000 m |
| Ambient Air Temperature for Operation | -20…60 °C |
| Ambient Air Temperature for Storage | -40…80 °C |
| Climatic Withstand | Conforming to IACS E10 |
| Fire Resistance | 960 °C conforming to IEC 60695-2-11 |
| Mechanical Robustness | Shocks: 30 Gn for 11 ms, Vibrations: 5 Gn, 5...150 Hz |
This circuit breaker is designed for motor protection and is used to safely interrupt the flow of electricity in the event of an overload or short circuit, protecting the motor from damage.
Yes, it is a 3-pole circuit breaker suitable for three-phase motor applications, providing protection across all three phases.
The rated current for this circuit breaker is 1 A, with a thermal protection adjustment range of 0.63 to 1 A.
The maximum rated operational voltage for this device is 690 V AC, making it suitable for a wide range of industrial applications.
It can be mounted on a 35 mm symmetrical DIN rail with a clip or screwed onto a panel using M4 screws.
The dimensions are 45 mm in width, 97 mm in depth, and 89 mm in height.
Yes, it has phase failure sensitivity, which helps to protect the motor in the event of a phase loss.
It has a high breaking capacity of 100 kA at 230/240 V AC, and the same at 400/415 V AC, 440 V AC, 500 V AC, and 690 V AC, conforming to IEC 60947-2 standards.
The circuit breaker has an IP20 degree of protection conforming to IEC 60529 and an IK04 degree of protection against mechanical impacts.
Yes, it meets several international standards including EN/IEC 60947-2 and EN/IEC 60947-4-1, and holds various product certifications such as CCC, UL, CSA, EAC, ATEX, LROS, BV, RINA, and DNV-GL.
The thermal protection adjustment range for this circuit breaker is from 0.63 to 1 A, conforming to IEC 60947-4-1.
Yes, it can be used as a manual motor starter, providing both protective and disconnect functions for motor control.
This content has been produced using multiple sources. EU Automation takes no responsibility for the accuracy of this information. Always consult the original equipment manufacturer for the most up to date instructions and information.
All parts new or reconditioned are covered by EU Automation 12 month warranty
No hassle returns policy
Dedicated customer support team
We understand that credit is a necessary part of business and offer credit agreements on request, subject to status.
Payment optionsWe accept Bank transfers and the following methods of payment:
All transactions are handled securely by HSBC and HSBC Merchant Services. For more information, please visit our dedicated payments page.
Global supplier of quality automation and control components
Dispose of your old unit by exchanging it for a working part.
A comprehensive repair service for faulty equipment.
Discover how we do our part to keep your production lines moving.