What type of device is this component?
It is a Siemens 3TH4 auxiliary contactor, also known as a contactor relay. It is designed to switch multiple auxiliary and control circuits within industrial control panels.
How many auxiliary contacts does it have?
The device provides nine auxiliary contacts: five normally open contacts and four normally closed contacts. It has no changeover contacts.
What does the contact configuration 5NO + 4NC mean?
It means the contactor relay has five normally open contacts that close when operated and four normally closed contacts that open when operated.
What control voltage does the coil require?
The coil requires a 220 V AC control supply and is rated for operation at both 50 Hz and 60 Hz.
Does this contactor relay include mechanical latching?
Yes. The unit has a mechanical latching mechanism, allowing it to retain its switched state mechanically rather than relying on continuous coil energisation.
What are its AC-15 operational current ratings?
For AC-15 control-duty applications, the rated operational current is 10 A at 230 V AC and 6 A at 400 V AC.
How is the device mounted?
It supports screw mounting and snap-on installation onto a 35 mm standard mounting rail in accordance with DIN EN 50022.
What type of electrical terminals are provided?
The auxiliary and control circuits use screw-type terminals, providing conventional wired connections for control-panel installation.
What are the component's dimensions?
The contactor relay measures approximately 55 mm wide, 78 mm high and 140 mm deep. These dimensions should be checked against the available panel space before installation.
What operating temperature range is specified?
The specified ambient operating temperature range is from -25°C to +55°C.
What is the front protection rating?
The front of the device is rated IP20, helping to prevent access by fingers and similarly sized solid objects when correctly installed.
What does the switching-element identification code 54 indicate?
The identification code 54 denotes the contact arrangement used by this auxiliary contactor: five normally open contacts and four normally closed contacts.
Are any contacts delayed or make-before-break?
No. The specified normally open and normally closed contacts are standard switching contacts, with no delayed, leading, lagging or make-before-break contact functions.
Where is this type of contactor relay commonly used?
It is commonly used in industrial control cabinets for interlocking, signalling, sequence control, status indication and multiplying control contacts.
What should be checked before replacing an existing contactor relay?
Confirm the 220 V AC coil voltage, 50/60 Hz frequency, 5NO + 4NC contact arrangement, mechanical-latching requirement, AC-15 current ratings, terminal style, mounting method and physical dimensions.