What type of component is this?
It is a three-pole motor-protective trip block designed for use with the PKZ2 motor-protective circuit-breaker system.
What is the adjustable overload setting range?
The overload release can be adjusted from 0.6 A to 1 A, allowing it to be matched to the rated current of a suitable motor.
What is the short-circuit release setting range?
The adjustable short-circuit release range is 8 A to 14 A. The catalogue data indicates a factory setting equivalent to 12 times the 1 A rated uninterrupted current.
How many poles does the trip block have?
The ZM-1-PKZ2 has a three-pole configuration for use in three-phase motor circuits.
Does it provide both overload and short-circuit protection?
Yes. The unit combines an adjustable overload release with an adjustable magnetic short-circuit release.
Is it sensitive to phase loss?
Yes. The catalogue identifies the trip block as having single-phasing sensitivity in accordance with IEC/EN 60947-4-1.
What is the rated uninterrupted current?
The rated uninterrupted current is 1 A.
Which circuit-breaker system is it intended for?
It is intended to operate as part of the PKZ2 motor-protective circuit-breaker system and should be paired with compatible PKZ2 components.
Can the current setting be selected to match a motor?
Yes. The overload dial can be set within the 0.6 A to 1 A range according to the motor nameplate current and the requirements of the installation.
What motor sizes can it be used with?
The applicable motor rating depends on supply voltage. Catalogue examples range from approximately 0.12 kW at 220–240 V to 0.55 kW at 660–690 V, subject to the motor's rated current remaining within the adjustable range.
Is it suitable for EEx e motor applications?
The catalogue lists this trip-block range as suitable for protecting EEx e motors. For such installations, the 95/96 normally closed contact must be used to de-energise the associated contact module or contactor.
What should be checked before fitting the component?
Confirm that the installation uses a compatible PKZ2 basic unit, that the motor rated current falls between 0.6 A and 1 A, and that the required short-circuit setting is within the available 8 A to 14 A range.