What is the voltage rating for this safety relay?
The Telemecanique XPS-AX5120 safety relay is rated for 24 V ac/dc, making it suitable for a variety of industrial control applications.
Can this safety relay be used for emergency stop applications?
Yes, the XPS-AX5120 is designed for use in emergency stop applications, as well as for monitoring limit switches and other safety devices.
What type of contacts does this safety relay have?
The XPS-AX5120 features 1 Normally Closed (NC) and 3 Normally Open (NO) contacts, providing flexibility for integrating into safety circuits.
How many safety circuits can this module monitor?
This safety relay can monitor up to three safety circuits, offering comprehensive protection for your machinery and processes.
What standards does the XPS-AX5120 comply with?
The safety relay complies with international standards such as IEC 204-1, EN 292, EN 418, and EN 60204-1, ensuring it meets global safety requirements.
Is there a visual indication of the relay's status?
Yes, the XPS-AX5120 is equipped with LED indicators that provide a visual status of the relay's operation and diagnostics.
What is the synchronisation time between inputs for this module?
The module has a synchronisation time of 75 ms for automatic starting, which is the time it takes to ensure all safety inputs are synchronised before starting a machine.
What type of connections does the XPS-AX5120 use?
The safety relay uses captive screw clamp terminals, which can accommodate cables without cable ends up to 4 mm2, or with cable ends up to 2 x 2.5 mm2.
What is the operating temperature range for this safety relay?
The operating temperature range for the XPS-AX5120 is from -10°C to +55°C, allowing it to function reliably in a wide range of industrial environments.
How can I integrate this safety relay into my existing safety system?
The XPS-AX5120 can be integrated into your existing safety system by connecting it to emergency stop buttons, safety gates, or light curtains, ensuring that it cuts power to machinery in the event of a safety breach.