What is the primary function of this safety relay?
The primary function of this safety relay is to monitor emergency stop and safety door circuits, ensuring safe operation in industrial environments.
What are the operating voltage requirements for this safety relay?
This safety relay operates at a control circuit supply voltage of 24 V AC/DC with a tolerance of -15% to +10%.
What type of contacts does this safety relay have?
This safety relay features 8 enabling current paths and 1 signalling current path, with contacts made of AgSnO2.
What is the maximum switching voltage for this safety relay?
The maximum switching voltage for this safety relay is 250 V AC/DC.
What is the typical response time for this safety relay?
The typical response time for this safety relay is less than 380 ms for automatic start and less than 60 ms for manual start.
What is the degree of protection for this safety relay?
The safety relay has a degree of protection rated at IP20, with a minimum installation location protection of IP54.
Can this safety relay be mounted in any position?
Yes, this safety relay can be mounted in any position on a DIN rail according to EN 60715.
What is the mechanical service life of this safety relay?
The mechanical service life of this safety relay is approximately 10 million cycles.
What is the maximum ambient operating temperature for this safety relay?
The maximum ambient operating temperature for this safety relay is 55°C.
What type of connection method is used for this safety relay?
This safety relay uses a screw connection method and is also pluggable.