What is the function of this thermal overload relay?
The thermal overload relay is designed to protect electric motors from overheating, ensuring that the current flowing to the motor does not exceed safe levels. It helps prevent motor damage due to excessive load by tripping the circuit when an overload is detected.
Can this relay be used with different types of motor protection?
Yes, it is suitable for motor protection applications and can be used in conjunction with fuses and circuit breakers to provide comprehensive protection for control circuits.
What are the mounting options for this relay?
The relay can be mounted on a plate with an EverLink power terminal block or on a rail with an EverLink power terminal block, providing flexibility for installation.
What is the tripping threshold of the relay?
The tripping threshold is set at 1.14 +/-0.06 times the rated current (In) conforming to IEC 60947-4-1, which helps ensure precise protection for your motor.
What is the surge withstand capacity of the relay?
The relay has a surge withstand capacity of 6 kV conforming to IEC 60801-5, which provides robust protection against voltage spikes.
Is the relay sensitive to phase failure?
Yes, it has phase failure sensitivity, with a tripping current of 30% of the rated current (Ir) on one phase, while the others are at Ir, conforming to IEC 60947-4-1.
What are the dimensions of the relay?
The dimensions of the relay are 121 mm in height, 75 mm in width, and 100 mm in depth, making it compact and suitable for various installation environments.
What is the operational voltage rating for this relay?
The rated operational voltage for the power circuit is 690 V AC 50/60 Hz conforming to IEC 60947-4-1.
What certifications does the relay have?
The relay is certified by several standards, including ATEX, CSA, and UL, among others, ensuring compliance with international safety and quality requirements.
What is the ambient air temperature range for the operation of the relay?
The relay can operate within an ambient air temperature range of -20 to 60 °C conforming to IEC 60947-4-1, allowing for use in a variety of environmental conditions.