| Part Number |
C10F32D040 |
| Manufacturer |
Schneider |
| Product Range |
ComPacT NSX new generation |
| Device Short Name |
NSX100F |
| Product Type |
Circuit breaker |
| Application |
Distribution |
| Poles Description |
3P |
| Protected Poles Description |
3D |
| Rated Current |
40 A at 40 °C |
| Rated Operational Voltage |
690 V AC 50/60 Hz |
| Network Type |
AC |
| Network Frequency |
50/60 Hz |
| Suitability for Isolation |
Yes, conforming to EN/IEC 60947-2 |
| Utilisation Category |
Category A |
| Rated Ultimate Short-Circuit Breaking Capacity |
85 kA at 220/240 V AC, 36 kA at 380/415 V AC, 35 kA at 440 V AC, 25 kA at 500 V AC, 22 kA at 525 V AC, 8 kA at 660/690 V AC, all conforming to IEC 60947-2 |
| Performance Level |
F 36 kA 415 V AC |
| Trip Unit Name |
Micrologic 2.2 |
| Trip Unit Technology |
Electronic |
| Trip Unit Protection Functions |
LSoI |
| Control Type |
Toggle |
| Mounting Mode |
Fixed |
| Rated Insulation Voltage |
800 V AC 50/60 Hz |
| Rated Impulse Withstand Voltage |
8 kV |
| Rated Service Short-Circuit Breaking Capacity |
85 kA at 220/240 V AC, 36 kA at 380/415 V AC, 35 kA at 440 V AC, 12 kA at 500 V AC, 11 kA at 525 V AC, 4 kA at 660/690 V AC, all conforming to IEC 60947-2 |
| Mechanical Durability |
50,000 cycles |
| Electrical Durability |
50,000 cycles at 440 V In/2, 30,000 cycles at 440 V In, 20,000 cycles at 690 V In/2, 10,000 cycles at 690 V In |
| Power Dissipation per Pole |
1.34 W |
| Mounting Support |
Backplate |
| Mounting Position |
Horizontal and vertical, flat on the back |
| Connection Type |
Front (upside and downside) |
| Connection Pitch |
35 mm |
| Protection Type |
L: for overload protection (long time), So: for short time short-circuit protection with fixed delay, I: for instantaneous short-circuit protection |
| Trip Unit Rating |
40 A at 40 °C |
| Long-Time Pick-Up Adjustment Type |
Ir (thermal protection), adjustable 9 settings |
| Long-Time Protection Pick-Up Adjustment Range |
18...40 A |
| Long-Time Protection Delay Adjustment Type |
tr, fixed |
| Long-Time Protection Delay Adjustment Range |
400 s at 1.5 x Ir, 16 s at 6 x Ir, 11 s at 7.2 x Ir |
| Thermal Memory |
20 minutes before and after tripping |
| Short-Time Protection Pick-Up Adjustment Type |
Isd, adjustable 9 settings |
| Short-Time Protection Pick-Up Adjustment Range |
1.5...10 x Ir |
| Short-Time Protection Delay Adjustment Type |
tsd, fixed |
| Instantaneous Protection Pick-Up Adjustment Type |
Ii, fixed |
| Instantaneous Protection Pick-Up Adjustment Range |
600 A |
| Earth-Leakage Protection |
Without |
| Zone Selective Interlocking (ZSI) |
Without |
| Number of Slots for Electrical Auxiliaries |
5 slots |
| Local Signalling |
Flashing LED (green) for ready to operate, LED 105% Ir (red) for overload, LED 90% Ir (orange) for overload |
| Width |
105 mm |
| Height |
161 mm |
| Depth |
86 mm |
| Net Weight |
2.05 kg |
| Standards |
EN/IEC 60947 |
| Product Certifications |
CCC, EAC, Marine |
| Overvoltage Category |
Class II |
| Electrical Shock Protection Class |
Class II |
| Pollution Degree |
3, conforming to IEC 60664-1 |
| IP Degree of Protection |
IP40, conforming to IEC 60529 |
| IK Degree of Protection |
IK07, conforming to IEC 62262 |
| Ambient Air Temperature for Operation |
-25…70 °C |
| Ambient Air Temperature for Storage |
-50…85 °C |
| Relative Humidity |
0…95% |
| Operating Altitude |
0...2000 m without derating, 2000 m...5000 m with derating |