What type of electrical component is this?
This is a Schneider Multi 9 C60N miniature circuit breaker designed to protect electrical circuits against overcurrent and short circuits.
What is the rated current?
The circuit breaker has a rated current of 10 A when calibrated at 25°C.
What is the rated operating voltage?
Schneider 60161 is rated for operation at up to 240 V AC.
How many poles does this circuit breaker have?
It is a two-pole circuit breaker, allowing two conductors to be disconnected together.
Which tripping characteristic does it use?
The unit uses a D-curve tripping characteristic. Its magnetic release operates at approximately 10 to 14 times the rated current.
What applications suit a D-curve circuit breaker?
A D-curve breaker is suited to loads that can produce high starting currents, including motors, transformers and similar inductive equipment.
What is the short-circuit interrupting rating?
The breaker has a short-circuit current rating of 10 kA at 240 V AC.
How is the unit mounted?
It can be installed on a standard 35 mm DIN rail and is also suitable for flush or surface mounting within compatible panels and enclosures.
What terminal arrangement is provided?
The device has box-lug terminals on both the line and load sides, intended for use with copper conductors.
What conductor sizes can be connected?
The listed conductor range for Schneider 60161 is 18 to 4 AWG. Installation requirements and terminal torque values should be checked before fitting.
What are the approximate dimensions?
The circuit breaker measures approximately 36 mm wide, 107 mm high and 76 mm deep.
What enclosure protection rating does it have?
The breaker case is rated IP40, while the terminals are rated IP20.
Which electrical standards does it meet?
The unit is listed to UL 489, certified to CSA C22.2 No. 5.1 and rated in accordance with IEC 60947-2. It is also CE marked.
Can the circuit breaker be reverse fed?
Yes. The Multi 9 C60 design permits reverse feeding, provided the installation complies with the applicable electrical requirements.
Can auxiliary devices be fitted?
Yes. The Multi 9 system supports compatible plug-on accessories such as auxiliary contacts, alarm switches, shunt-trip modules and undervoltage releases.
What operating temperature range applies?
The specified operating temperature range is -30°C to 70°C, with calibration based on an ambient temperature of 25°C. Rating adjustments may be necessary at higher temperatures.