What are the main features of this bus module?
The B&R X67AI1323 bus module features four analogue inputs with a 12-bit digital converter resolution, capable of handling input signals ranging from 0 to 20 mA or 4 to 20 mA. It includes short-circuit protection and configurable digital input filters.
What is the protection rating of this module?
The B&R X67AI1323 bus module has an IP67 protection rating, making it suitable for use in harsh environments where dust and water resistance are required.
What are the operating temperature limits for this module?
The operating temperature range for the B&R X67AI1323 is from -25°C to 60°C, ensuring reliable performance in a variety of industrial settings.
How is the module connected to the system?
The module connects to the system using M12 connectors for the X2X Link and I/O connections, ensuring secure and reliable connectivity.
What is the power consumption of the module?
The B&R X67AI1323 bus module has an internal power consumption of 3 W for I/O and 0.75 W for the X2X Link supply.
What type of input signals can this module handle?
This module can handle differential input signals in the range of 0 to 20 mA or 4 to 20 mA, with a maximum allowable input signal of ±30 mA.
What is the isolation voltage between the input and the bus?
The isolation voltage between the input and the bus for the B&R X67AI1323 is 500 V, providing robust protection against electrical interference.
What is the maximum altitude for operation without temperature derating?
The B&R X67AI1323 can operate at altitudes up to 2000 meters above sea level without any temperature derating. Above 2000 meters, the ambient temperature should be reduced by 0.5°C for every additional 100 meters.