What type of circuit protection does this device provide?
The A9F92204 is an Acti9 iC60L miniature circuit breaker with thermal-magnetic protection. It protects circuits against overloads and short circuits and has two protected poles.
What are the rated current and tripping characteristic?
The rated current is 4 A, and the breaker has a Z-curve tripping characteristic. Its magnetic tripping limit is specified as three times the rated current, with a tolerance of ±20%.
Can this circuit breaker be used on both AC and DC networks?
Yes. The datasheet specifies suitability for AC and DC networks, with AC operation at 50/60 Hz. Breaking capacity varies with the network voltage and applicable standard, so the relevant rating must be checked for the intended circuit.
What is the short-circuit breaking capacity?
The rated short-circuit capacity is 15 kA at 400 V AC under EN/IEC 60898-1. Under EN/IEC 60947-2, the ultimate breaking capacity is 100 kA at 380–415 V AC, 70 kA at 440 V AC and 20 kA at up to 125 V DC.
How is the circuit breaker mounted?
The breaker is designed for fixed installation on a DIN rail. It occupies four 9 mm pitches and supports compatible comb busbar and distribution block connections at either the top or bottom.
What are the dimensions and weight?
The unit measures 85 mm high, 36 mm wide and 78.5 mm deep. Its stated net weight is 0.25 kg.
What conductor sizes can the terminals accept?
The top and bottom terminals accept rigid conductors from 1 to 25 mm² and flexible conductors from 1 to 16 mm². The specified wire stripping length is 14 mm, and the terminal tightening torque is 2 N·m.
Does the breaker include earth-leakage protection?
Earth-leakage protection is not built into this miniature circuit breaker. The datasheet specifies a separate block for this function.
How can the operating status be checked locally?
The breaker has a toggle control, a contact position indicator and a local trip indicator, allowing its status to be checked at the device.
What environmental conditions is the breaker rated for?
The specified operating temperature range is −35°C to +70°C, and the storage temperature range is −40°C to +85°C. The rated operating altitude is up to 2,000 m, and the degree of protection is IP20.
What are the stated mechanical and electrical endurance ratings?
The datasheet lists mechanical endurance of 20,000 cycles and electrical endurance of 10,000 cycles. These are endurance ratings rather than a prediction of service life in a particular installation.
Is the circuit breaker suitable for isolation?
Yes. The A9F92204 is specified as suitable for isolation under EN/IEC 60947-2. It also has a rated insulation voltage of 500 V AC and a rated impulse withstand voltage of 6 kV.