What type of electrical component is this?
This is a Schneider Acti9 iC60H miniature circuit breaker designed to protect electrical distribution circuits against overloads and short circuits.
How many poles does this circuit breaker have?
It is a three-pole circuit breaker with protection provided across all three poles, making it suitable for three-phase electrical circuits.
What is the rated current?
The A9F84350 has a rated current of 50 A.
What does the C tripping curve mean?
The C curve provides thermal-magnetic tripping and is commonly used for circuits with moderate inrush currents. Its magnetic tripping threshold is approximately eight times the rated current, with a tolerance of ±20%.
What is the breaking capacity at 400 V AC?
The circuit breaker has a rated short-circuit capacity of 10 kA at 400 V AC under IEC and EN 60898-1. Under IEC and EN 60947-2, its ultimate breaking capacity is 15 kA at 380–415 V AC.
Can this circuit breaker be used with both AC and DC networks?
Yes. It is specified for AC and DC networks, although the applicable breaking capacity varies according to the operating voltage and standard.
How is the device mounted?
The device uses fixed mounting on a standard DIN rail. Its 54 mm width occupies six 9 mm module pitches.
What are the dimensions of the circuit breaker?
The unit measures approximately 85 mm high, 54 mm wide and 78.5 mm deep.
What conductor sizes can be connected?
The terminals accept rigid conductors from 1 to 35 mm² and flexible conductors from 1 to 25 mm². The specified stripping length is 14 mm, and the terminal tightening torque is 3.5 Nm.
Does the circuit breaker indicate when it has tripped?
Yes. It includes local trip indication as well as a contact-position indicator, helping operators distinguish the device's operating state.
What is the operating temperature range?
The specified ambient operating temperature range is -35°C to 70°C. The storage temperature range is -40°C to 85°C.
What ingress protection rating does it have?
The circuit breaker has an IP20 rating in accordance with IEC and EN 60529.
What are its rated insulation and impulse withstand voltages?
The rated insulation voltage is 500 V AC, while the rated impulse withstand voltage is 6 kV.
Is it suitable for electrical isolation?
Yes. The A9F84350 is suitable for isolation in accordance with IEC and EN 60898-1 and IEC and EN 60947-2.
What is the expected mechanical and electrical endurance?
The specified mechanical endurance is 20,000 operating cycles, and the electrical endurance is 10,000 cycles.
Can residual-current protection be added?
Residual-current protection is not integrated into this miniature circuit breaker, but it can be provided using a separate compatible earth-leakage block.