steve
Got hold of Sime for a Carrier card for…
Got hold of Sime for a Carrier card for a chiller. Machine down in a factory. Received the new card in express time machine and plant now up and running fantastic service form Sime
3 weeks ago
Full 12-month warranty
Available for dispatch immediately
We deliver worldwide
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
All orders are subject to product availability. See our T&Cs.
Ask our team
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
| Specification | Description |
|---|---|
| Product Brand Name | SENTRON |
| Product Designation | Switch disconnector |
| Design of the Product | EMERGENCY-STOP switch |
| Number of Poles | 4 |
| Mechanical Service Life | 100,000 operating cycles |
| Electrical Endurance | 6,000 operating cycles at AC-23 A at 690 V |
| Operating Frequency | Maximum 50 operations per hour |
| Degree of Pollution | 3 |
| Insulation Voltage | Rated value 690 V |
| Surge Voltage Resistance | Rated value 6 kV |
| Operating Voltage | Rated value 690 V at AC |
| Operating Frequency | 50 Hz to 60 Hz |
| Protection Class | IP65 |
| NEMA Rating | 1, 3R, 4X, 12 |
| Power Loss | 0.5 W per pole in hot operating state |
| Operational Current | 16 A at AC-21 at 690 V, 240 V, 400 V, 440 V; 16 A at AC-23 A at 400 V |
| Operating Power | 4 kW at AC-23 A at 240 V; 8 kW at AC-23 A at 400 V; 7.5 kW at AC-23 A at 440 V; 8 kW at AC-23 A at 690 V; 3 kW at AC-3 at 240 V; 6 kW at AC-3 at 400 V; 5.5 kW at AC-3 at 690 V |
| Auxiliary Circuit | No CO, NC, or NO contacts; Maximum operating voltage 500 V; Continuous current 10 A; Insulation voltage 500 V |
| Suitability | Main switch, switch disconnector, EMERGENCY OFF switch, safety switch, maintenance/repair switch |
| Product Feature | Can be locked into OFF position |
| Short Circuit | Conditional short-circuit current 50 kA at 690 V with gG fuse; Let-through current 3 kA at 240 V, 440 V, 690 V; I2t value 2.5 kA².s at 240 V, 440 V; 3 kA².s at 690 V |
| Design of the Fuse Link | Required fuse gL/gG: 20 A for main circuit; 10 A for auxiliary switch |
| Operational Current (UL) | 16 A at AC according to UL 508/UL 60947-4-1 |
| Operating Voltage (UL) | 600 V at AC at 50/60 Hz according to UL 508/UL 60947-4-1 |
| Active Power (UL) | 7.5 hp at 480 V; 10 hp at 600 V according to UL 508/UL 60947-4-1 |
| Short-Time Withstand Current (UL) | 5 kA at 600 V according to UL 508/UL 60947-4-1 |
| Connections | Solid conductor: 1x (1...6mm²); Finely stranded with core end processing: 1x (1...4mm²); Stranded: 1x (1..6mm²); Auxiliary contacts: Solid 2x (0.75 ... 2.5 mm²), 1x 4 mm²; Finely stranded: 2x (0.75 ... 1.5 mm²), 1x 2.5 mm²; Stranded: 2x (0.75 ... 2.5 mm²), 1x 4 mm² |
| Type of Electrical Connection | Box terminal for main current circuit; Connection terminals for auxiliary contacts |
| Mechanical Design | Height: 84 mm; Width: 67 mm; Depth: 116.5 mm; Fixed mounting; Front mounting with central attachment |
| Net Weight | 207 g |
| Environmental Conditions | Operating temperature: -25 °C to 55 °C; Storage temperature: -25 °C to 55 °C |
This Siemens part functions as a switch disconnector, designed for emergency switching-off applications.
The rated operational current for this switch disconnector is 16 A at AC-21 and AC-23 applications.
Yes, this switch is designed to be used as an EMERGENCY-STOP switch.
The mechanical service life of this switch disconnector is typically 100,000 operating cycles.
This switch disconnector offers a protection class of IP65, making it suitable for various environmental conditions.
The dimensions of this switch disconnector are 84 mm in height, 67 mm in width, and 116.5 mm in depth.
Yes, this switch disconnector is suitable for use as a main switch.
The maximum operating power at 400 V for this switch is 8 kW at AC-23 A.
This switch disconnector supports front mounting with central attachment.
The rated insulation voltage for this switch disconnector is 690 V.
This content has been produced using multiple sources. EU Automation takes no responsibility for the accuracy of this information. Always consult the original equipment manufacturer for the most up to date instructions and information.
All parts new or reconditioned are covered by EU Automation 12 month warranty
No hassle returns policy
Dedicated customer support team
We understand that credit is a necessary part of business and offer credit agreements on request, subject to status.
Payment optionsWe accept Bank transfers and the following methods of payment:
All transactions are handled securely by HSBC and HSBC Merchant Services. For more information, please visit our dedicated payments page.
Global supplier of quality automation and control components
Dispose of your old unit by exchanging it for a working part.
A comprehensive repair service for faulty equipment.
Discover how we do our part to keep your production lines moving.