What type of device is this?
It is a fixed-mount, thermal-magnetic (TMD) moulded case circuit breaker designed for AC power distribution applications.
How many poles does it have?
It is a 3-pole device with 3 protected poles (3P3D), suitable for three-phase circuits.
What is the rated current?
The rated current is 125 A at 40 °C (In = 125 A).
What is the rated operational voltage and frequency?
It is rated up to 690 V AC at 50/60 Hz for AC networks.
What protection functions does it provide?
It provides LI protection: overload protection (L, thermal) and short-circuit protection (I, magnetic).
Is the long-time (overload) setting adjustable?
Yes. The long-time pickup (Ir) is adjustable from 0.7 to 1.0 times the rated current (In).
What are the short-circuit interruption capabilities?
The rated ultimate short-circuit breaking capacity (Icu) is 25 kA at 380/415 V AC; it is also rated 40 kA at 220/240 V AC, 20 kA at 440 V AC, and 15 kA at 500 V AC (per IEC 60947-2).
What is the instantaneous (magnetic) trip level?
The instantaneous pickup (Ii) is fixed at 1250 A.
Does it include earth-leakage protection?
No. Earth-leakage protection is not included on this unit.
Can it be used as an isolator?
Yes. It is suitable for isolation in accordance with EN/IEC 60947-2.
How is it mounted and connected?
It is a fixed (non-drawout) circuit breaker intended for backplate mounting. Connections are made from the front, with a 35 mm connection pitch.
What are the physical dimensions and weight?
Approximate dimensions are 105 mm (W) × 161 mm (H) × 86 mm (D), with a net weight of about 2.2 kg. (These values correspond to C16B3TM125.)
What environmental ratings does it have?
It is rated IP40 (IEC 60529) and IK07 (IEC 62262), with an operating ambient range of -25 to 70 °C and storage range of -50 to 85 °C.
How many auxiliary accessory slots are available?
It provides 5 slots for electrical auxiliaries, allowing integration of compatible signalling and auxiliary functions.