What type of device is this?
It is a fixed-mount earth-leakage circuit breaker for AC distribution, combining overcurrent and earth-leakage protection in a single unit. This device uses an electronic trip unit (MicroLogic 4.2 Vigi).
What electrical network is it designed for?
It is intended for AC networks at 50/60 Hz, with a rated operational voltage up to 440 V AC.
How many poles does it have and what does the pole configuration mean?
It is a 3-pole device with 3D (three protected poles), meaning all three phases are protected by the trip unit.
What is the rated current and can it be adjusted?
The trip unit rating is 100 A at 40 °C, and the long-time pickup (Ir) is adjustable across 9 settings from 40 A to 100 A.
What protection functions are included?
It provides: L (overload/long-time), So (short-time with fixed delay), I (instantaneous), and R (earth-leakage) protection functions.
What are the short-circuit breaking capacities at common voltages?
Its rated ultimate short-circuit breaking capacity (Icu) is 25 kA at 380/415 V AC, 20 kA at 440 V AC, and 40 kA at 220/240 V AC (per IEC 60947-2).
Is the earth-leakage sensitivity adjustable?
Yes. Earth-leakage sensitivity (IΔn) is adjustable across 30 mA, 100 mA, 300 mA, 500 mA, 1 A, 3 A, and 5 A, and can also be set to OFF using the IΔn rotary switch.
Can the earth-leakage time delay be adjusted?
Yes. The earth-leakage time delay (Δt) is adjustable with settings of 0 ms, 60 ms, 150 ms, 500 ms, and 1 s.
What are the key short-time and instantaneous trip settings?
Short-time pickup (Isd) is adjustable from 1.5 to 10 × Ir with a fixed short-time delay (tsd) of 0.02 s. Instantaneous pickup (Ii) is fixed at 1500 A.
How is it mounted and how are connections made?
It is a fixed circuit breaker designed for backplate mounting. Connections are front-connected (upside and downside), with a 35 mm connection pitch.
What are the enclosure and environmental ratings?
It is rated IP40 and IK07. Typical operating ambient range is -25 to 70 °C, with storage from -50 to 85 °C, and it is specified for operation up to 2000 m without derating (2000 m to 5000 m with derating).
Are there any built-in status indications?
Yes. It includes local LED indications: a green flashing LED for ready-to-operate, an orange LED at 90% Ir for overload, and a red LED at 105% Ir for overload.
What are the physical dimensions and approximate weight?
Overall dimensions are approximately 105 mm (W) × 161 mm (H) × 86 mm (D), with a net weight around 2.05 kg.
Does it support electrical auxiliaries?
Yes. The unit provides 5 slots for electrical auxiliaries (availability and selection depend on the required auxiliary function).
Does it provide isolation capability?
Yes. It is suitable for isolation in accordance with EN/IEC 60947-2.
What does “Class A” earth-leakage protection indicate?
Class A earth-leakage protection is designed to detect residual currents for AC and pulsating DC components, making it suitable for many modern loads where non-sinusoidal leakage can occur.